Request for
Proposal
Air Handling
Units
Posted
03/09/2011
Proposals
are due by COB
3/23/2011
The proposal will include air handling unit, outdoor grill and wall sleeve for 54 units. Price will include Delivery. The units will run in cool mode 365 days a year but units will be required to have room freeze protection which activates at a room temperature of 40 degrees F or below. The vendors ability meet customers schedule will need to be discussed. Since no onsite work will be required vii, viii, xii, xiv should not apply. The equipment contract on the RFP home page will be used for this proposal.
Furnish air-cooled through-the-wall
package terminal air conditioners and heat pumps (assembled in the USA).
Units are rated in accordance with the ARI (Air Conditioning &
Refrigeration Institute) Standards 310/380-93, CSA (Canadian
Standards
Association) EEV certification programs and ETL listed.
Ratings
Each unit must meet the following specifications:
ARI rating of 15,000 BTUH cooling (and 13,300 BTUH
reverse cycle heating with a COP of 2.9 at 47¡ F O.D.)
Electric resistance heat of 13,900 BTUH. Total Amp draw
must be of 7.0 Amps and 1465 Watts at 230/208 volts.
The unit must remove a minimum of 4.4 pints of
moisture per hour when operated at rating conditions. The EER
must be a minimum of 9.9 EER.
Unit
Chassis
Each unit must be slide out design shipped with room cabinet
front installed. Unit chassis must have the ability to be installed
with 0 clearance from finished floor. An electrical power cord
must be included with chassis and installed by the manufacturer
to assure proper NEMA 6 or 7 configuration and UL-approved
length. Units less than 250 volts must also have a LCDI power cord.
Unit must be tested for conformance to ASTME water infiltration
specification ASTME 331-86, which ensures no water infiltration
when tested
at 8" rain per hour at 63 mph wind for 15 minutes
Room
Cabinet
The monochromatic front of the room cabinet must be able to
be field-secured to chassis to inhibit tampering. Filter must be
accessible without removing room front. Cabinet depth must
not exceed 7⅝Ó to minimize unitÕs impact on room space.
Coils
UnitÕs coils must have rifled copper tubing expanded into
rippled-edge louvered aluminum fins. Exterior coil must be of
a two-row slab coil design with removable shroud top to allow
easy-access for cleaning of the exterior coil.
Heat
Pumps
Each unit must include a change-over thermistor that senses an
outside ambient switch-over temperature as low as 24¡F, lockopen
refrigerant reversing valve during heat pump operation,
temperature-activated defrost drain and automatic emergency
heat operation to override the heat pumpÕs change-over
thermostat and bring on electric resistance heaters in the event
of a sealed system failure. Unit must not operate compressor
and
electric heaters simultaneously.
Compressor
The compressor must be hermetically sealed, internally isolated,
rotary-type and permanently mounted on rubber isolators. No
removal or adjustment of compressor hold-down bolts is to be
required during installation.
Warranty
The warranty is for Full One Year on the entire unit; Full 2nd through
5th Year on the entire sealed refrigerant system components;
Limited
Second through Fifth Year on functional parts only.
Evap
orat or/Condenser Fans
Direct drive with a permanent, split-capacitor, two-speed indoor
motor. Condensate must be directed onto the back and sides of
the coil to aid in evaporation and removal.
Air
Discharge
Must be a sloped surface so that obstructions cannot be placed
on the unit. Discharge conditioned air can be directed into the
room at an angle of 16 or 56 degrees from the vertical position.
The discharge grille must be of polycarbonate material to resist
bending,
cracking, rusting and corrosion.
Wall
Sleeves (WS900E)
The wall sleeve must be industry-accepted dimensions: 14⅛Ó
depth x 42Ó width x 16¹/₁₆Ó height and constructed of
G90 HDG
galvanized steel with a baked corrosion-inhibiting urethane
primer and baked-polyester topcoat enamel. Sleeve must be
insulated and shipped with a weather resistant rear closure
panel
installed.
Outdoor
Grilles
Outdoor grille must be architecturally extruded, louvered
aluminum (AGK01*B), one-piece polymer-blend injection
molded louver (PGK01*B) or standard stamped aluminum
(SGK**B). All other grilles must be submitted to the PTAC
manufacturer for feasibility, airflow characteristics and
compliance
with UL regulations, where necessary.
Other proposal requirements:
i. Terms for breach. Proposals must provide for administrative, contract or legal remedies for any breach or violation of the contract terms by the Vendor and appropriate remedial action.
ii. Termination clause. Proposals must include a termination clause indicating the manner by which termination will be effected and the basis for settlement. In addition, the clause will describe the conditions under which the contract may be terminated by default and the conditions under which the contract may be terminated for circumstances beyond the control of the Vendor.
iii. Access to documents. Proposals must include a provision permitting PTC, the Department of Commerce, the Comptroller General of the US, or any of their duly authorized representatives to have access to any books, documents, papers and records of the Vendors applicable to the Project for the purpose of making audits, examinations, excerpts and transcriptions.
iv. Contract Work Hours and Safety Standards Act (40 U.S.C. ¤¤ 327, 333). Proposals involving construction work or work that includes the employment of mechanics or laborers must include a provision for compliance with Sections 102 and 107 of the Contract Work Hours and Safety Standards Act (40 U.S.C. 327, 333), as supplemented by Department of Labor regulations (29 CFR Part5).
v. Clean Air Act (42 U.S.C. ¤ 7401 et seq.) and the Federal Water Pollution Act (33 U.S.C. ¤1251 et seq.). Proposals must contain a provision agreeing to abide by the Clean Air Act and the Federal Water Pollution Act.
vi. Byrd Anti-Lobbying Amendment (31 U.S.C. ¤ 1352). All Vendors must file the Byrd Anti-Lobbying Amendment certification, certifying that the Vendor will not and has not used Federal appropriated funds to pay any person or organization for influencing or attempting to influence an officer or employee of any agency, a member of congress, office or employee of Congress, or an employee of a member of Congress in connection with obtaining any Federal contract, grant or any other award covered by 31 U.S.C. ¤ 1352.
vii. Equal Employment Opportunity. Proposals must include a provision requiring compliance with Executive Order (ÒE.O.Ó) 11246, ÒEqual Employment Opportunity,Ó as amended by E.O. 11375, ÒAmending Executive Order 11246 Relating to Equal Employment Opportunity,Ó and as supplemented by regulations at 41 CFR Part 60, ÒOffice of Federal Contract Compliance Programs, Equal Employment Opportunity, Department of Labor.Ó
viii. Copeland ÒAnti-KickbackÓ Act (18 U.S.C. ¤ 874 and 40 U.S.C. ¤ 276c). Proposals for contracts greater than $2,000 in construction or repair must include compliance with the Copeland ÒAnti-KickbackÓ Act.
ix. Debarment and suspension (E.O.s 12549 and 12689): Proposals must include a statement indicating that the Vendor is not listed in the General Services AdministrationÕs List of Parties Excluded from Federal Procurement or Non-procurement Programs in accordance with Executive Orders 125449 and 12689.
Please check site often for updates. If planning to submit a proposal please email rfp@pine-net.com and you will be emailed when the site is updated. Please email all questions or concerns to email address above. PTC reserves the right to modify, change or cancel this RFP at any time. PTC has the right to refuse all proposals.